| • Generator set specification |
40 KVA |
| Model |
GPWII-PII-40X |
| Duty |
Prime |
| Power Rating kVA / kWe |
40 / 32 |
| No of Phases |
3 phase |
| Output Voltage (V) |
415 |
| Power Factor (ɸ) |
0.8 |
| Frequency (Hz) and RPM |
50, 1500 |
| • Engine Specification |
|
| Make |
ESCORTS |
| Model |
G40-II |
| MoEF Certified Power (KW) |
42.8 |
| Cooling type |
Water Cooled |
| Type of Aspiration |
TCAC |
| No. of cylinders |
4, Inline |
| Bore (mm) x Stroke (mm) |
91 x 110 |
| Starting system |
12 V DC |
| Lube oil specification |
API CI4, 15W40 |
| • Alternator Specification |
|
| Make |
CG, Stamford |
| Type |
2P, Rotating Field |
| Current ( Amps) |
55.64 |
| Voltage regulation (Max.) |
± 1 % |
| Class of Insulation |
H |
| Enclosed Genset Dimensions ( Length x Width x Height) in mm |
1425 X 930 X 1320 |
| Wet Weight in KG |
1260 |
| Standard Fuel Tank Capacity ( in Ltr) |
85 |