200 KVA Mahindra Generator

  • 200KVA Prime (Closed type) Mahindra Diesel Generating set closed coupled with Stamford Alternator with standard accessories.

Inquiry Now
50 Hz PrimeRating(kVA)200
Rated (KWe)160
Engine ModelmPower62485G
No of Cylinders6
Phase / Voltage (V)3 / 415
Power Factor0.8 (lagging)
Current (A)174
Frequency (Hz)& RPM50/1500
Governing classG2 as per ISO 8528 Part V
Starting system24 V DC Elec
Fuel tank capacity400
Canopy dimensions w/o silencer (mm) (L x W x H) approx.4500 x 1400 x 1800
Genset Weight (kg) approx.2800
Engine Specification
Make / SeriesMahindra mPower
Rated Power at 100% Load @ 1500 RPM (HP)248
AspirationTurbocharged Aftercooled
Bore x Stroke (mm)105 x 137
Displacement (Lit)7.2
Fuel consumption @ 75% load (lit/hr) ^33.3
Fuel consumption @ 100% load (lit/hr) ^40.8
Lube oil specification15W40 API CI4+
Total lubrication system capacity (lit)20.2
Lube oil consumption @ 100% load ($)0.1% of Fuel Consumption
Lube oil change period (hrs.)500
Radiator coolant capacity (liter)24
Rated Speed(RPM)1500
Rated Engine Power KW (HP)180
244.6
Rated Current(AMP) Capacity @ 0.8PF1 PhaseNA
3 Phase278.2
Cooling SystemWater Cooled
DimensionLength4300
Width1400
Height1800
Intergrated Fuel Tank Capacity (lits)390
Approximate Weight of DG set (Kg)2800
Alternator
Enclosure TypeIP23
Voltage regulation±1%
Class of insulationClass H
Maximum Unbalanced Load across Phases25%
  • Supplied with all Standard Accessories  i.e. Genset Controller, Battery & leads, Anti-Vibration pads, Safety Switches for LLOP, HWT etc. ( For More information please refer Brochure attached).
Weight2800 kg
Dimensions430 × 140 × 180 cm
Open and Closed Type

Phase

SKU: ET200MGEN3 Category: Tags: ,

Quick Inquiry